What limits this battery is its rather than its 100 Ah: 100 A continuous and 150 A for 3 s. Behind a 48 V inverter that is at most 3,641 W of steady load before the 15 % margin is gone, because the inverter draws its power divided by 50.4 V and by an efficiency we cap at 85 %.

A 2000 W inverter pulls 46.7 A, so it needs 1 of these in parallel; one 5.12 kWh bank of them stores 4,096 Wh usable at 80 % depth of discharge.

On its own it holds a weekend van (400 Wh a day) load for 10.2 days and the year-round van profile (895 Wh) for 4.6 days, with no sun at all. Its 100 A charge limit also caps the solar side: one battery accepts about 5,760 W of panels behind an at 57.6 V charging voltage, so a bigger array needs a second battery or a controller set to limit current. Without a heater it stops accepting charge below 0.0 °C, which the checker flags for any location whose design low is colder.

Add to a build

Largest inverter it carries

Max inverter = BMS continuous × 0.85 × 50.4 V × 0.85 efficiency. Surge checked against the BMS peak where both are published.
Batteries in parallelBMS continuousMax inverterInverters in the catalog that fit
1 ×100 A3,641 WVictron Energy MultiPlus 48/3000/35 (2,400 W), Victron Energy MultiPlus-II 48/3000/35-32 230V (2,400 W)
2 ×200 A7,283 WVictron Energy MultiPlus 48/5000/70 (4,000 W), Victron Energy MultiPlus-II 48/5000/70-50 230V (4,000 W)
3 ×300 A10,924 WVictron Energy MultiPlus-II 48/10000/140-100 230V (8,000 W), Victron Energy MultiPlus-II 48/8000/110-100 230V (6,400 W)

Datasheet

FieldValue
Capacity100 Ah at 51.2 V
BMS continuous / peak100 A / 150 A, 3 s
Max charge100 A
Charge below0.0 °C
Depth of discharge80 %, 6,000 cycles

Source: manufacturer documentation

Similar batteries

Where to buy

As an Amazon Associate and through direct retailer programs, this site earns from qualifying purchases — see how.

No direct manufacturer program is joined yet (§13.3); prices marked with an image and a dollar figure are a specific listing checked via the Amazon Creators API, the rest are plain searches.

How this page was computed

Inverter DC draw = watts ÷ (50.4 V under load × 0.85). A pairing passes when that draw stays at or below 85 % of the combined BMS continuous rating and the surge draw stays under the BMS peak.

The formulas are the same open engine the checker runs; the methodology page lists every constant.

These results are for reference. Wiring must be installed by a qualified electrician. Mobile installations follow ABYC E-11; stationary ones NEC 690/706.